Medium-voltage switching, a 3.6 MVA transformer, and low-voltage distribution all set into a single factory-built skid.

Contact sales

Inside the skid

The complete skid seen from the ring main unit corner, with the transformer and low-voltage switchboard visible along the common steel base.
Power path
In this configuration, power enters through the ring main unit. The transformer steps the voltage down, and the switchboard distributes power to the IT rows.

Skid specifications

Electrical

Transformer rating
3.6 MVAKNAN
Output voltage (AC)
480 V / 277 V or 415 V / 240 V3-phase, 4-wire, 60 Hz, solidly grounded wye
Incoming voltage (AC)
35 kV class standardOther MV ratings available
Switchboard
UL 891 constructionConfigurable output designs

Factory and site

Factory test scope
Full L3 and partial L4
Enclosure
NEMA 3R · outdoor rated
Nominal dimensions
(L × W × H)
25 ft × 9.5 ft × 10 ftOverall height varies with equipment.
Shipping weight
~45,000 lb

Monitoring

EPMS integration
Ignition 8.3+One Ethernet uplink per skid
Integration target
Redfish API
Specified protocols
IEC 61850 MMS/GOOSEModbus TCP
The switchboard, transformer, and medium-voltage switchgear in profile on their common steel base.
Rear elevation
The medium-voltage end of the same skid, with two flanged pipes and cable trays visible beneath the deck.
Medium-voltage end

Skid drawings

Front elevation of the 25 ft nominal skid, with the ring main unit on the left, transformer in the middle, and low-voltage switchboard on the right.
Front elevation
Plan view showing the ring main unit, transformer, and switchboard along the full length of the common skid.
Plan view
Medium-voltage end elevation showing the enclosure, transformer behind it, and connections below the deck.
Medium-voltage end elevation

Discuss your deployment

Share your power requirements, site, and target date.